FAE-F 4 24 V AC/DC CAN
CAN module with 4 temperature and 4 voltage inputs. It is suitable for recording temperatures with Ni1000 or PT1000 sensors and voltages of, for example, electrical vent and mixing valves, valve positions, etc. The fieldbus module is an input module for universal use. It is controlled by means of the CAN bus. The module is addressed by means of an adjustable address, and the input states are transmitted in data bytes. If there is one (or more) analog output module(s) with the same address in the system, the voltage measured there is issued at the respective output. Each input can be adjusted either from 0 to 10 V DC, to Ni1000 (-50 °C to 150 °C), PT1000 (-50 °C to 150 °C) or PT1000 (0 °C to 400 °C) by means of a DIP switch.
- Connection with spring clamp terminal blocks (push-in)
- 3D-Data - Registration required -
- Mounting note
- Data sheet
Additional Information