KMA-E08

Description

The analog encoder is used as encoder for manual control variable definition, e.g. mixing valves, valve positions, temperature values, etc. The module can be operated in two modes, which can be commuted by means of integrated two-level switches (HAND, AUTO). The switch position is signalized by external control contact terminals S1 and S2. The control variable can be set on the potentiometer at the front. The output signal 0 to 10 V is available on the Y terminal. If the switch is in AUTO position, the control variable is looped through over the YR terminal to the Y output without change.

  • Setpoint device
  • Manual control level with checkback
  • LED brightness proportional to control variable
Technical Data
General Data
24 V AC/DC
24 mA
19 mA
0 V to 10 V DC
0 V to 10 V DC
Red LED
22.5 x 61.3 x 60 mm
70 g
-10 °C to +50 °C
-25 °C to +70 °C
IP40 / IP20
Check US distributor inventory
Part number
110660
4250184122937
× Do you have any questions?