EUW-C18 230 V AC

Description

Monitoring of direct or alternating voltages in live systems. It is displayed whether the adjusted values are exceeded or not reached, and a switching process is triggered. The integrated 7-segment display indicates the sources of the fault. The voltage to be measured (AC or DC), two measuring ranges, an upper and a lower threshold value, a response delay and the fault memory (ON or OFF) can be adjusted manually on the device. Faults can be acknowledged directly on the device or by means of an external contact.

  • Connection with screw type terminal blocks
Technical Data
General Data
230 V AC, 50 Hz
max. 15 mA
10 V to 300 V
1 V to 100 V
0.1 s to 9.9 s, adjustable
2 x changeover contacts (DPDT)
max. 250 V AC
max. 8 A
3 x 107 switching cycles
1 x 105 switching cycles
2 x 7-segment displays
Green and red LED
50 x 69.3 x 60 mm
200 g
-5 °C to 55 °C
-20 °C to 70 °C
IP40 / IP20
Check US distributor inventory
Part number
11027405
4250184120995